Submitted by admin on Thu, 10/19/2017 - 15:06
SUPPORT TYPE CURRENT TRANSFORMERS
36 kV
Block Type Design Standard: IEC 60044-1/6, VDE0414, ANSI, GOST
On request with capacitive later
On request with barrier |
|
Technical Data
Type
Rated data |
|
AB36-1 |
AB36-3 |
AB36-T1 |
AB36-T3 |
Operating voltage
(maximum) |
(kV) |
36 |
Test voltages |
(kV) |
70/170 |
Rated frequency |
(Hz) |
50 or 60 |
Maximum rated primary current |
(A) |
3000 |
Secondary rated current |
(A) |
1 or 5 |
Rated short-time thermal current lth (1s) |
(kA) |
max. 60 ( max. 1000 x ln ) |
Rated dynamic current ldyn |
(kA) |
max. 120 ( 2.5 x lth ) |
Weight ( approx ) |
(kg) |
42 |
52 |
46 |
56 |
|
Other specifications possible on request.